Call 1.866.433.8335 for a friendly customer service representative who can customize your commercial kitchen ventilation hood system complete with exhaust fan, make up air heater or supply air package, fire suppression system, electrical control package, stainless grease duct and more, while providing you a fast quotation including submittal drawing packages. Our product line includes ETL and ANSI listed commercial kitchen ventilation hood systems, commercial kitchen exhaust fans, heaters, make-up air units, grease rated ductwork, motors and more all with a one year warranty.
|
| SPECIFICATION |
|
| Model: |
VPCU |
| |
| Description: |
Unit shall be factory assembled pollution control unit capable of significantly reducing smoke,
grease, and odor from the exhaust air stream.
|
|
| Certifications: |
Unit shall be listed by ETL and conforms to UL710 in both US and Canada.
|
|
| Construction: |
|
| Housing |
|
The PCU housing is to be constructed of 430 SS of polish 2B or better. All metal in contact with the
air-stream is to be constructed of 430SS. 1500°F Ceramic based gasket must be in place for all internal
seams exposed to airflow. High temperature weatherproofing gasket must be used on all exterior seams.
|
| |
| Base |
|
The base shall be constructed of galvanized steel for improved rigidity. Base shall be structurally reinforced
to accommodate the filter assembly.
|
| |
| Pre-Filter Section |
|
The pre filter section shall include 4 inch deep steel washable permanent filters. Filter
frames and media shall be constructed of steel. Filters shall be arranged in a v-bank
configuration to increase filter area and reduce static pressure. All filters shall be
removable without the use of tools through side access doors with lift and turn latches.
Filters are to be cleanable with a water hose and soapy water. The filters shall have a
minimum average arrestance of 75% in accordance with ASHRAE 52.1-1992.
|
| |
| High Efficiency Filter Section |
|
The phase two filters shall consist of 4 inch deep rigid cell extended surface filters. Filter cell sides
shall be constructed of high strength, high impact polystyrene plastic for durability. Beverage board filter
sides shall not be permitted. Filters shall be arranged in a v-bank configuration to increase filter area and
reduce static pressure. All filters shall be removable without the use of tools through side access doors with
lift and turn latches. Filters are to be rated MER14 minimum in accordance with ASRAE standard 52.2 and have a
minimum average arrestance of 98% in accordance with ASHRAE 52.1-1992. High Efficiency module must be installed
downstream of pre-filter module.
|
| |
| Odor Control Media Section (Optional) |
|
The unit shall be provided with a 50% potassium permanganate 50% carbon blend media. The odor removal
cartridges shall be encased in steel frames. The odor removal media shall be arranged in a v-bank
configuration to increase filter area and reduce static pressure. All media shall be removable without
the use of tools through side access doors with lift and turn latches. Odor control module must be installed
downstream of High Efficiency module or HEPA module.
|
| |
| Product: Fan shall be model VPCU as manufactured by Ventilation Direct. |
| |
|
|