Direct-Fired Formulas
|
|
|
Heating Requirements
|
| Input BTU/Hr = |
|
(Blower SCFM * Temp Rise * Density Factor) / .92 |
|
|
|
| Temp Rise = |
|
(Input BTU/Hr * .92)
|
|
Blower SCFM * Density Factor
|
|
|
|
| Density Factor = |
|
1.08 +
| (70-Blower Temp) * .024
|
|
10
|
|
|
|
|
|
Output BTU/Hr
|
| Output BTU/Hr = |
|
Input BTU/Hr * .92
|
|
|
|
|
|
Profile Velocity
|
| Profile Velocity = |
|
945 * sqrt(Profile Pressure / 0.075)
|
|
|
|
|
|
Burner Areas
|
| 6 Inch Straight = | .32 sq ft. |
| 12 Inch Straight = | .65 sq ft. |
| T Section = | .77 sq ft. |
| Ell Section = | .65 sq ft. |
|